Structure and Floor Plan:
» |
5,500 square feet
of available data center space with the capacity
to expand to over 9,000 square feet |
» |
Industry-standard
hard floors covered by vinyl tile and overhead
wiring systems for better cooling capability and
more secure cable infrastructure |
» |
Built to surpass
local area building codes and seismic
requirements |
Robust Electrical System Including:
» |
Incoming commercial power
service routed underground to a dedicated
transformer |
» |
300 kVA Powerware 9315
centralized UPS with redundant battery cabinets
|
» |
Over 4 hours of UPS runtime on
battery backup at current load |
» |
313 kVA standby Cummins diesel
generator (Automatically activated by transfer
switch) |
» |
Over 24 hours of runtime on
generator before requiring additional fuel at
full load |
» |
Liebert Precision power
distribution unit |
» |
UPS full maintenance bypass
allows for power upgrades and UPS service
without interruption of power to equipment |
Security:
» |
Complete network IDS
(Intrusion Detection System) monitors data and
network security transparently through an
optical tap |
» |
Closed circuit security camera
system covering all building and data center
entrances along with integrated motion detection
systems |
» |
Six to eight weeks of security
data is retained at all times |
» |
Access to facility is
restricted to technical staff employees |
Established, Reliable Network:
» |
Full OC3c connectivity to
Verio with contracts signed for a Cable &
Wireless OC3c |
» |
Cisco 7206 VXR border router
with NPE 400 with redundant backup 7206 VXR on
standby |
» |
Cisco 3550 Catalyst backbone
switch |
» |
Hewlett-Packard Procurve rack
switches |
» |
Network VLan segmented by
customer type and use |
Climate Control:
» |
Liebert Precision 22 ton up
flow air conditioning |
» |
Regulates temperature and
humidity precisely for optimal server stability
|
» |
Air filtration systems remove
dust and foreign particulates from circulation
|
» |
Independent compressors and
cooling loops enhance redundancy |
» |
Capacity for over 120 Tons of
Cooling |
|
|
|
|
|
|
|